Technical data:
SCHEIDT SYSTEM NZ 210-240
Rated capacity: | max. 630 kVA¹ | |
External dimensions: | ||
W: 2.10 m | L: 2.40 m | H: 2.39 m |
Dimensions inside: | ||
W: 1.81 m | L: 2.11 m | H: 2.14 m |
Total weight empty:² | about 7.48 t | |
Roof weight: | about 1.76 t | |
Built-up area: | 5.04 m² | |
Constructed space: | 12.05 m³ | |
Effective area: | 3.82 m² | |
Station stop: | Rd30 | |
Roof anchorage: | Rd16 | |
Standard door dimensions | Light door dimension | Light door dimension |
Standard dimensions | Steel doors | Aluminum doors |
W: 1850 x H: 1320 mm | W: 1760 x H: 1230 mm | W: 1790 x H: 1185 mm |
W: 1695 x H: 1605 mm | W: 1605 x H: 1230 mm | W: 1635 x H: 1185 mm |
W: 1000 x H: 1105 mm | W: 930 x H: 1015 mm | W: 955 x H: 970 mm |
¹ Installed rated capacity depending on the transformer losses
and the ventilation technology used.
² Empty weight depending on the station structure.