NZ 173-283 Technical data, dimensions

You are here: / Start / Products / Turnkey stations / SCHEIDT System NZ / NZ 173-283 Technical data, dimensions

SCHEIDT SYSTEM NZ

Non-walk-in stations, cell construction

The SCHEIDT SYSTEM NZ 173-283 in detail.

SCHEIDT SYSTEM NZ 173-283
SCHEIDT SYSTEM NZ 173-283

Technical data:

SCHEIDT SYSTEM NZ 173-283

Rated capacity: max. 630 kVA¹
External dimensions:
W: 1.73 m L: 2.83 m H: 2.43 m
Dimensions inside:
W: 1.49 m L: 2.59 m H: 2.20 m
Total weight empty:² about 6.48 t
Roof weight: about 1.72 t
Built-up area: 4.90 m²
Constructed space: 11.90 m³
Effective area: 3.86 m²
Station stop: Rd30
Roof anchorage: Rd16
Standard door dimensions Light door dimension Light door dimension
Standard dimensions Steel doors Aluminum doors
W: 1695 x H: 1320 mm W: 1605 x H: 1230 mm W: 1635 x H: 1185 mm
W: 1490 x H: 1320 mm W: 1400 x H: 1230 mm W: 1430 x H: 1185 mm
W: 1000 x H: 1105 mm W: 930 x H: 1015 mm W: 955 x H: 970 mm

¹ Installed rated capacity depending on the transformer losses
and the ventilation technology used.

² Empty weight depending on the station structure.